Related Products






Cable duct fireproof partition sealing kit
Welding - rectangular
The first innovative technology in China
Cable tray safety guardian
Fireproof isolation products made of high-performance fireproof materials, consisting of fireproof fiber cloth
A combined metal frame sprayed with fireproof paint and a flame-retardant expansion block.
Product Content

T SWS-X+X...X×N -AO Frame

TSC-M Series Module

TSC-E Series blind plug module

Tensioner

SL-55 Grease

Interlayer
Product characteristics
Fire Rate level | GB23864>1h、A-0、A-60 |
Protection leve | IP68 |
Watertightness | 0.3MPa |
Airtightness | 0.3MPa |
Lifespan | 30 years |
Customized product services
Cable/pipe sealing solutions that meet diverse needs can provide customized products and services.

Flexible application to different Dimensions of cables and pipes

EMC Solutions for electrical safety

For explosion protectionin hazardous areas solution

Suitable for armoured cable solution

be used in fresh water, chilledwater and waste water pipelines

be installed in wet conditions and running water

Non-welding solutions are available

Built-in spare capacity, easy to install Upgrade and renovate

Suitable for under ground application solution
Our Advantages
- 20 years of experience
- Source factory
- OEM/ODM customization
- Fast production and
- delivery
- Multiple patented
- technologies
- Comply with IATF16949
- ISO9001 standards
- Total factory area 50,000 m²
- Fireproof and waterproof
- EMI/EMP electromagnetic shielding
- Lifespan up to 30 years
Product Parameters
Product Overview
Usage Environment
Ambient temperature: -45℃~150℃℃
Ozone concentration: *100ppm
Humidity: 0~100%
Protective shell bearing weight: *5kg
Flame-retardant expansion material and flame-retardant sponge
Flame-retardant expansion material is a solid flat plate, which expands when heated (temperature 160℃),
Expansion ratio>500%, after preheating and expansion, its shape changes to flocculent material, and forms a completely
Incombustible carbon layer. The flocculent material formed by expansion will wrap around the cable surface, fill the gap between the cable and the metal
frame, and achieve flame retardant function.
Metal structural parts
Use 2mm galvanized sheet
Surface sprayed with fire retardant paint
Technical standards
Comply with the following standard documents:
GB 50217-2018
“Electric Power Engineering Cable Design Standard”
GB 50872-2012
“Hydropower Engineering Design Fire Protection Code”
GB 23864-2009 “Fireproof Sealing Materials”
In the early stage of fire, when the temperature rise does not reach 160℃,
the fireproof cloth arranged on both sides of the fire-blocking section can
prevent the flame from transferring to the other side (back of fire), thus achieving the function of blocking the initial fire.
Related Certifications
TST SEAL have undergone rigorous testing and inspection: chemical analysis, aging test, vertical combustion test, acetic acid salt spray test, toxicity test, watertight and airtight performance test, electrical strength test, dust and vibration resistance test, corrosion resistance test, fire retardant performance test, noise resistance performance test, etc.